CONTENTS CONTENTS

Products

The products listed here are for overseas markets, not for Japan domestic.

CONTEC Thermocouple Module CONPROSYS I/O Module / 4ch CPS-SSI-4C

Compatible with various types of thermocouple inputs. Cold junction compensation function within

The CPS-SSI-4C is an expansion I/O module that adds a thermocouple interface to the CPU unit of the CONPROSYS series. Four channels of differential inputs are provided for one module.

Thermocouple Module CONPROSYS I/O Module / 4ch

Model:

CPS-SSI-4C

Maker:

CONTEC Co., Ltd.

Features

  • Compatible with various types of thermocouple inputs
    This product is compatible with a wide range of thermocouple input types such as J(IEC60584-1), K(IEC60584-1), E(IEC60584-1), N(IEC60584-1), R(IEC60584-1), S(IEC60584-1), and T(IEC60584-1).
  • Cold junction compensation function within
    As cold junction compensation is integrated in the product, there is no need to install a temperature sensor for cold junction compensation externally, and temperature can be measured simply by connecting a thermocouple.
  • Adaptable to a wide range of temperature between -20 to 60°C (-4°F to 140°F)
    The product is capable of operating in the temperature between -20 to 60°C (-4°F to 140°F). It can be installed in the various environments.
  • Installation easy with two pieces of terminal support and DIN rail
    You can install and remove a terminal connector without a screwdriver so that it can shorten the time of the replacement. As the product can be not only mounted on DIN rail, but also is removable along the side rails, replacing is simple and easy as well.
  • Equipped with the LED for an operation check
    The product has LED for an operation check, which helps you visually confirm the communication status of each interface.
  • No electrolytic capacitor
    Without an electrolytic capacitor, which has a limited life, we are creating the product with a longer life.

Specifications

Item Description
Input type Differential input
Input channel 4ch
Resolution 24-bit
Conversion speed *1 251ms (Conversion speed per thermocouple per channel)
Buffer memory The latest data only
Compatible thermocouple sensor J (IEC 60584-1), K (IEC 60584-1, JIS C1602), E (IEC 60584-1), N (IEC 60584-1), R (IEC 60584-1), S (IEC 60584-1), T (IEC 60584-1)
Conversion tolerance Thermocouple type K, J, E, N, T:
Within ±[0.3°C + Measured temperature x 0.12% (0°C or higher) or 1% (0°C or lower)
Thermocouple type R, S:
Within ±[1.2°C + Measured temperature x 0.12%]
Allowable signal source resistance 300Ω or less *3 *4
Cold junction sensor Integrated
Cold junction tolerance *2 Within 3.6°C
Isolation Bus isolation
Isolation withstand voltage 500VDC
Connector 3.81mm pitch 10-pin terminal
Applicable wire AWG30 – 16
LED Status (Green, Red)
Electricity consumption 0.1A (Max.)
Physical dimensions (mm) 25.2(W)×94.7(D)×124.8(H) (No projection included)
Weight 200g
Installation method Quick mounting on the 35mm DIN rail

*1 It is the conversion time of the measurement value. Communication time is not included.
*2 It is the measured value under the condition of wind speed of 0 – 0.5m/s in the thermostatic bath.
*3 If the resistance value of the wiring distance (round trip) exceeds the allowable signal source resistance value, an error exceeding the conversion error specification may occur.
*4 If the cable length exceeds 30 m, it is not CE (EMC standard) compliant.

Get Adobe' Reader'

To view the pdf files, the Adobe Reader from Adobe Systems is required.

Researched by Shared Research Inc.
about Nihon Denkei Co., Ltd.