This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.
Products
The products listed here are for overseas markets, not for Japan domestic.
RS-485 based Robust remote I/O module for Modbus-RTU protocol : 10ch 16bit Thermocouple Input. Over-voltage Protection
The CONPROSYS Robust I/O series is a standalone remote I/O module that supports the Modbus communication protocol. It is designed to be environmentally resistant, with excellent noise resistance and overvoltage and overcurrent protection circuits, and can be used in industrial applications such as monitoring factory equipment and production lines and process control.
Modbus-RTU RS-485 Remote I/O 6ch 16bit RTD Input with Open Wire Detection - CONPROSYS Robust I/O Seires
Model:
CPSR-M7015G
Maker:
CONTEC Co., Ltd.
Features
- RS-485 based Robust remote I/O module for Modbus-RTU protocol : 6ch 16bit RTD Input with Open Wire Detection
RS-485 (Modbus-RTU) based remote I/O with 6ch 16bit RTD Input. Communication control system of up to 1.2 km can be constructed using low-cost twist-pair cable. - Over-voltage Protection
Digital input channels feature high overvoltage protection, preventing the module from being damaged by high voltage spikes or incorrect wiring. - Designed for a wide operating temperature range of -25 to 75°C (-13 to 167°F)
Designed to withstand a wide operating temperature range of -25 to 75°C (during operation) (-13 to 167°F). Robust design that can be used in outdoor environments with large temperature changes. - Dual watchdog function monitors module and communication failures
Dual watchdog function monitors module and communication failures. If the module detects an operational fault, it will automatically reset. - Robust ESD resistance
Passed IEC 61000-4-2 ESD testing, the rugged design is resistant to noise, spikes and high voltage electrostatic discharges.
Specifications
Add-on Module
| Series | CONPROSYS Robust I/O |
|---|---|
| Bus Specification | RS-485 (Modbus-RTU) |
| Size | – |
| Used Connector | – |
Sensor Input
| Type | RTD |
|---|---|
| Input Channels | Differential 6-ch |
| Compatible Sensor | Pt100; Pt1000; Ni120; Cu100; Cu1000 |
| ADC Resolution | 16-bit |
| Sampling Rate | 83.3msec (12Hz) |
Digital I/O
| Input Channels | – |
|---|---|
| Output Channels | – |
| Bi-directional I/O Channels | – |
| Response Time (Input) | – |
| Response Time (Output) | – |
| Operating Voltage (Input) | – |
| Operating Voltage (Output) | – |
| Input Circuit | – |
| Output Circuit | – |
| Built-in Power Supply | – |
Counter
| Number of Channels | – |
|---|---|
| Counting System | – |
| Response speed | – |
Supported OS
| Supported OS | – |
|---|
System specifications
| Item | Description | |
|---|---|---|
| CPU Module | Watchdog Timer | Module, Communication (Programmable) |
| Isolation | Intra-module Isolation | 3000 VDC |
| EMS Protection | EFT (IEC 61000-4-4) | ±4 kV for Power Line |
| ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal | |
| LED Indicators | Status | 1 x Power and Communication |
| Analog Input | Channels | 6 |
| Type | RTD | |
| Sensor Type | Pt100, Pt1000, Ni120, Cu50, Cu100, Cu1000 | |
| Resolution | 16-bit | |
| Accuracy | ±0.05% of FSR | |
| Sampling Rate | 12 Hz (Total) | |
| Overvoltage Protection | 120 VDC | |
| Individual Channel Configuration | Yes | |
| Open Wire Detection | Yes | |
| COM Ports | Ports | 1 x RS-485 |
| Baud Rate | 1200 – 115200 bps | |
| Data Format | (N, 8, 1), (N, 8, 2), (E, 8, 1), (O, 8, 1) | |
| Protocol | Modbus RTU | |
| Power | Reverse Polarity Protection | Yes |
| Input Range | +10 – +30 VDC | |
| Consumption | 1.1W | |
| Mechanical | Dimensions (mm) | 72(W) x 122(L) x 34(H) |
| Installation | DIN-Rail Mounting | |
| Environment | Operating Temperature | -25 – +75 °C |
| Storage Temperature | -40 – +85°C | |
| Humidity | 10 – 95% RH, Non-condensing | |
| Standard | VCCI Class A, FCC Class A, CE Marking (EMC Directive Class A, RoHS Directive), UKCA |