This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.
Products
The products listed here are for overseas markets, not for Japan domestic.
Customized pneumatic fixtures are available for different transformer pin configurations. It also supports PC connectivity.
The MICROTEST 5460 Series Transformer Tester is an all-in-one device designed for measuring important parameters of transformer products. It enables measurements of parameters such as inductance, leakage inductance, DC resistance, AC resistance, quality factor, capacitance, turns ratio, and pin short circuit detection. The measurement frequency range spans from 10Hz to 200k/500k/1MHz. The tester is equipped with built-in support for LCR meter measurement mode and comes with the F5468 pneumatic testing fixture. It provides 48 testing channels and supports 100mA DC bias testing. Customization services are available to tailor the tester to meet specific customer requirements.
Transformer Tester 5460 Series
Model:
5465, 5466, 5467
Maker:
MICROTEST Corporation
Features
- Test Frequency: 10Hz-200kHz/500kHz/1MHz
- 48 Channels
- Built-in Meter Mode
- Simultaneously display four parameters
- Basic accuracy up to ±0.1%
- Open circuit/short circuit function
- RS-232、Handler、LAN、USB Host 、EXT.I/O
- Pneumatic fixture
- F5620 built-in 100mA DC Bias
- USB Host storages can storage setting files, data and capture the screen
Detecting Essential Electrical Parameters of Transformers
Specifications
| Model | 5260 Series | ||
| Test Channel | 48 | ||
| Test Frequency | 10Hz-200kHz | ||
| Other | 5465 | 5466 | 5467 |
| 10Hz-200kHz | 10Hz-500kHz | 10Hz-1MHz | |
SPEC
| Frequency Resolution | 5 digits | |
| Basic Accuracy | ±0.1% | |
| AC Drive Level | 10mV-2Vrms | |
| DC Drive Level | 10mV-2V | |
| Output Impedance | 100Ω | |
| DC Bias Current | 100mA (F5620) | |
| Turn |
Inductance or Voltage Test Freqeuncy:50Hz-200kHz |
|
| Test Mode | Meter Mode / List Mode | |
| Parameters Measurement | Inductance (L)、Impedance (Z)、Capacitance (C)、Resistance (R)、Conductance (G)、Susceptance (B)、Admittance (Y)、Alternating Current Resistance (ACR)、Quality Factor (Q)、θ、Direct Current Resistance (DCR)、Leakage Inductance、Turn Ratio、Balance、Short Circuit | |
Parameters
| Parameters | Range |
Basic Accuracy (AC parameter:1kHz) |
Speed |
| L, LK | 0.1nH ~ 9999.99H | 0.1% | 25ms |
| C | 0.00001pF ~ 999.99mF | 0.1% | 25ms |
| Q,D | 0.00001 ~ 99999 | 0.0005 | 25ms |
| Z,X,R | 0.00001Ω ~ 99.9999MΩ | 0.1% | 25ms |
| Y | 0.01nS ~ 99.9999S | 0.1% | 25ms |
| θ | -180°~ +180° | 0.03° | 25ms |
| DCR | 0.1mΩ ~ 99.999 MΩ | 0.1% | 25ms |
| Turn | 0.1 ~ 99999.9 turns | 0.5% | 50ms |
| Pin-Short | 12 pairs, between pin to pin | – | 15ms |
System
| ESR | Series / Parallel |
| Calibration | Open Circuit / Short Circuit |
| Built-in storage | testing files 128 sets |
| Operation | Auto / Manual / Remote Trigger |
| Power Supply | Voltage:98Vac-132Vac or 195Vac-264Vac |
| Frequency:47-63Hz | |
| Power consumption | 300VA |
| Environment | Temperature:10℃-40℃ |
| Humidity:10-90%RH | |
| Dimension (W*H*D) | 344x145x343 mm (W*H*D) |
| Weight | 9 Kg |
| Interface | RS-232、Handler、LAN、USB Host、EXT. I/O |
| Display | 800*480 Color Screen, 7″ TFT |