CONTENTS CONTENTS

Products

The products listed here are for overseas markets, not for Japan domestic.

CONTEC Digital input Modbus-TCP Remote I/O 16ch (isolated 5-50VDC) CONPROSYS Robust I/O Series CPSR-ET7051

Ethernet based Robust remote I/O module for Modbus-TCP protocol : 16ch Digital Input (Couter). Over-voltage Protection

The CONPROSYS Robust I/O series is a standalone remote I/O module that supports the Modbus communication protocol. It is designed to be environmentally resistant, with excellent noise resistance and overvoltage and overcurrent protection circuits, and can be used in industrial applications such as monitoring factory equipment and production lines and process control.

Digital I/O Modbus-TCP Remote I/O 8ch/8ch (isolated 10-50VDC / 10-40VDC) CONPROSYS Robust I/O Series

Model:

CPSR-ET7051

Maker:

CONTEC Co., Ltd.

Features

  • Ethernet based Robust remote I/O module for Modbus-TCP protocol : 16ch Digital Input (Couter)
    Ethernet (Modbus-TCP) based remote I/O with 16ch Digital Input. Communication control system can be constructed using generic LAN cables.
  • Over-voltage Protection
    Digital input channels feature high overvoltage protection, preventing the module from being damaged by high voltage spikes or incorrect wiring.
  • Designed for a wide operating temperature range of -25 to 75°C (-13 to 167°F)
    Designed to withstand a wide operating temperature range of -25 to 75°C (during operation) (-13 to 167°F). Robust design that can be used in outdoor environments with large temperature changes.
  • Dual watchdog function monitors module and communication failures
    Dual watchdog function monitors module and communication failures. If the module detects an operational fault, it will automatically reset.
  • Robust ESD/EFT resistance
    Passes IEC 61000-4-2 ESD and IEC 61000-4-4 EFT tests. Robust design that is resistant to noise, spikes and high-voltage electrostatic discharges.

Specifications

Add-on Module

Series CONPROSYS Robust I/O
Bus Specification Ethernet (Modbus-TCP)
Size –
Used Connector –

Digital I/O

Input Channels 16-ch (possible to allocate counter)
Output Channels –
Bi-directional I/O Channels –
Response Time (Input) –
Response Time (Output) –
Operating Voltage (Input) 10 to 50VDC
Operating Voltage (Output) –
Input Circuit Opto-isolated input (for both current sink and source output)
Output Circuit –
Built-in Power Supply –

Supported OS

Supported OS –

System specifications

Item Description
Software Built-in Web Server Yes
CPU Module Watchdog Timer Module, Communication (Programmable)
2-Way Isolation Ethernet 1500 VDC
I/O 2500 VDC
EMS Protection EFT (IEC 61000-4-4) ±4 kV for Power Line
ESD (IEC 61000-4-2) ±4 kV Contact for Each Terminal, ±8 kV Air for Random Point
LED Indicators Status Run, Ethernet
Ethernet Ports 1 x RJ-45, 10/100 BASE-TX
Access Control ID, Password and IP Filter
Protocol Modbus TCP, Modbus UDP
Power Reverse Polarity Protection Yes
Consumption 2.1W (Max.)
Powered from Terminal Block +10to +30VDC
Mechanical Dimensions (mm) 72(W)x 123(L)x 35(H)
Installation DIN-Rail mounting
Environment Operating Temperature -25 -+75 °C
Storage Temperature -30 -+80 °C
Humidity 10 -90% RH, Non-condensing
Standard VCCIClass A, FCC Class A, CE Marking (EMC Directive Class A, RoHS Directive), UKCA