CONTENTS CONTENTS

ITEMLIST

Products Infomation

NOISEKEN Voltage Dip and Swell Simulator VDS-2002

Conforming to IEC 61000-4-11

A simulator to reproduce voltage variation phenomena in commercial power supplies (AC100V/200V).
This type of immunity test against voltage variation phenomena is defined in IEC 61000-4-5 and is widely used in many industries.

Voltage Dip and Swell Simulator

Model:

VDS-2002

Maker:

NOISE LABORATORY CO.,LTD.

SPECIFICATIONS

Items Specifications
Number of lines Single phase
Test mode Interruption
AC/DC
Local Synchronous: Short circuit
PC Synchronous: Short circuit/ Open circuit
Asynchronous: Short circuit/ Open circuit
Dip and swell Local Synchronous
PC Synchronous/ Asynchronous
Variation Local Asynchronous
(Only 2s-1s-2s standard defined test is available.)
PC Asynchronous
Input voltage range AC90~264V, 50/60Hz, DC0~125V
Output voltage range AC 0%~ 120% of input voltage, AC290V Max
DC 0V-input voltage
Output VA 4.224KVA (Continuous)
Output current capability AC 100% of input voltage: 16A rms (Continuous)
80% of input voltage: 20A rms (<5S)
70% of input voltage: 23A rms (<5S)
40% of input voltage: 40A rms (<5S)
DC 16A (Continuous)
Peak inrush current drive capability AC 100~ 120V: >250A (at 100% output, <10mS)
AC 220 ~240V: >500A (at 100% output, <10mS)
Load regulation 100% of input voltage 0-16A rms: <5%
80% of input voltage 0-20A rms: <5%
70% of input voltage 0-23A rms: <5%
40% of input voltage 0-40A rms: <5%
Overshoot/ undershoot <5% (100 ohm loaded)
Rise time/ fall time 1 ~ 5 µS (100ohm loaded)
Normal voltage setting Setting by percent Local 100%
PC (4%) ~120% /10V minimum
Setting by voltage PC 10V~290V/ 5V step
Accuracy ±5V (0V~16A output)
Dip/swell level Setting by percent Local Short circuit for 0% (Interruption), setting: 0/40/70/80/120% (5 steps)
PC Short/Open selectable for 0% (interruption): 0~120%
Setting by voltage PC Short/Open selectable for 0V (interruption): 0~290V(0~120%), 5V step
Accuracy ±5V
Repetition of events (No. of events) Local 1,3, 5, 10, 30, 50,100, or continuous (8 steps)
PC 1~1,000 or continuous (1 event step)
Interval cycle Setting by cycle Local 1, 3, 5, 10, 30, 50, 100, 300, 500 cycles and 10s (10steps)
PC 0.5 ~ 5,000.5 cycles (0.5 cycle step)
Setting by time Setting for short duration PC Synchronous: 1~100s (1s step)
Asynchronous: 8.3ms~100s (0.1m step)
Setting for long duration PC Asynchronous: 1s ~ 10h (1s step)
Dip cycle Setting by cycle Local 0.5, 1, 5, 10, 12, 25, 30, 50, 250, 300 cycles (10 steps)
PC 0.01 ~ 5,000 cycles (0.01 cycle step)
Setting by time Setting for short duration PC Synchronous: 0.1ms~100s (0.1ms step)
Asynchronous: 0.1ms~100s (0.1ms step)
Setting for long duration PC Asynchronous: 1s ~ 10h (1s step)
Dip
(starting phase angle of events)
Setting by phase angle Local Synchronous: 0,45,90,135,180,225,270,315 (8 steps, 45 degrees step)
PC Synchronous: 0~359° (1° step)
Setting by time PC Synchronous: 0~19.9 ms for 50 Hz (0.1ms step)
0~16.6 ms for 60 Hz (0.1ms step)
Voltage variation test Setting by time PC Asynchronous:
Changing time: 0.1s~10s (0.1s step) , At least 0.1s required for 10% change of input
Changed time: 0~10s (0.1s step)
Interval: 0~100s (0.1s step)
Test level: 0~120%
Memory Local 5 tests
PC 10 steps (Test sequence stored up to 10 steps when controlled by PC.)
Equipment Input voltage AC100~240V ±10%, 50/60Hz, 120VA
External interface Optical RS-232
Dimensions 430(W) x 745(H) x 600 (D) mm (Projection excluded)
Weight Approx. 150 kG

Get Adobe' Reader'

To view the pdf files, the Adobe Reader from Adobe Systems is required.

Researched by Shared Research Inc.
about Nihon Denkei Co., Ltd.