This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.
ITEMLIST
Products Infomation
AC LEAKAGE CLAMP METER CM4003 (Output and external power supply function)
Prevent unexpected downtime!
Identify potential problems and avoid large problems
AC LEAKAGE CLAMP METER
Model:
CM4003
Maker:
HIOKI
Feature
- Easily transfer measurement data to your smartphone or tablet by using our free app GENNECT Cross or to an Excel® file. (Wireless Adapter Z3210 is necessary)
- Complies with the performance standard set forth in IEC/EN 61557-13, an international standard on leak clamp meters
- Output function (waveform/RMS): use with a recorder to record waveforms and fluctuations
- Detect minuscule leakage currents with a newly designed sensor. (Core jaw diameter up to φ 40 mm)
- Solve GFCI and RCD problems quickly
- External power supply: use an optional AC adapter for continuous, long-term measurement
- Broad measurement range extending from leakage currents to load currents
- Speed up pass/fail judgments with the built-in comparator function
- CAT III 300 V
Product Video
Specification
AC Current range | 6.000 mA, 60.00 mA, 600.0 mA, 6.000 A, 60.00 A, 200.0 A, 6 ranges, True RMS Basic accuracy 45 Hz – 400 Hz: ±1.0% rdg ±5 dgt (6.000 mA to 6.000 A), ±1.5% rdg ±5 dgt (60.00 A, 200.0 A) Basic accuracy 15 Hz – 45 Hz, 400 Hz – 2 kHz: ±2.0% rdg ±5 dgt Defined accuracy range: 0.060 mA to 200.0 A |
AC Voltage range | N/A |
Frequency range | 15.0 Hz to 2000 Hz |
Crest factor | 3 (other than 200.0 A range), 1.5 (200.0 A range) |
Filter function | Cut off frequency: 180 Hz ±30 Hz at filter ON (-3 dB) |
Output function | RMS (RMS value output), WAVE (waveform output) |
Harmonic levels | [With Z3210 installed] Current harmonic levels up to 30th, Content factor, Total harmonic distortion ratio *Harmonics can be displayed with our free app GENNECT Cross. |
Other functions | Max/ Min/ AVG/ PEAK MAX/ PEAK MIN value display, Display value hold and auto hold; Backlight, Auto power save, Buzzer sound, Event count display, Comparator, Simple event recording, Rush current measurement |
Display | Display refresh rate: 5 times/s |
Power supply | – AA-size alkaline battery (LR6) × 2; Continuous operating time: 48 hr. (without Z3210 installed), 30 hr. (with Z3210 installed and using wireless communications) – AC Adapter Z1013 (5 V DC, 2.6 A) |
Core jaw diameter | φ 40 mm (1.57 in.) |
Dimensions and mass | 64 mm (2.52 in) W × 233 mm (9.17 in) H × 37 mm (1.46 in) D, 400 g (14.1 oz.) |
Included accessories | Connection Cable L9097 × 1, USB Cable × 1, Carrying case C0203 × 1, Instruction manual × 1, Operating Precautions × 1, AA-size alkaline battery (LR6) × 2 |