This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.


ITEMLIST
Products Infomation

The Ene-phant series is developing products centering on the regenerative function. All of them support customers with high efficiency and fulfilling functions.
The regenerative DC power supply "NT-AD-50K-B series", which can reuse valuable electric power, applies regeneration technology based on the achievements of Keisoku Giken to achieve efficiency of 90% or more, which is the highest level in Japan. Bidirectional power supply. It can be expanded with standard products up to 250 kW in 50 kW units.
Regenerative DC power supply (bidirectional) 50kW
Maker:
KEISOKU GIKEN
Features
Space-saving contributes to the ground area
For the 50kW single unit, the width has been reduced by 150mm and the depth by 100mm compared to the previous model, and the installation area ratio has been reduced by approximately 0.31m2. Both the area ratio and the volume ratio contribute to space saving of about 30%, and flexible installation is possible.

Regeneration efficiency of 90% or more, the highest level in the industry
Achieves high efficiency of 90% or more (at rated load). Furthermore, if the rated power is 15% or more, a regenerative efficiency of 80% or more is achieved. Highly efficient regeneration is possible over a wide range of load power.

Expandable up to 5 units of 250 kW! Series-parallel combination enables high voltage and large current
If it is the same model, you can connect up to 2 units in series like batteries (excluding 1500V models) and up to 5 units in parallel connection. Depending on the stage of evaluation and testing, a flexible configuration can be realized using a master/slave unit, from capacity expansion by combining multiple units to individual operation of multiple units.

Realizes seamless bi-directional and 0V drive
Seamless ±current bi-directional operation is possible without range switching from 0V.
Employs electrical insulation using a transformer
Electric insulation is provided between the power supply and the system using a transformer. Safe and secure design.
high speed operation
High-speed current response speed of 10msec or less and seamless power running (drive: power supply) and regeneration (absorption: load) switching are realized. Therefore, there is no overshoot or undershoot of the current, so you can use it safely without giving unexpected stress to the test piece.

Compliant with grid connection regulations
Equipped with system monitoring and protection functions that comply with the grid connection protection device certification test, it has the same monitoring and protection functions as general commercial power conditioners, and can circulate energy safely and without waste. can. Various system monitoring functions can be set to arbitrary values.

Oscilloscope-like operability
Adopts oscilloscope button layout and operability. The function pasted on the button image on the LCD screen is switched, enabling intuitive operation.

Regenerative power noise CISPR Class A compliant
Regenerative power noise complies with Class A. It has low noise so that there is no influence such as operation failure on other devices due to regenerative power noise.

Body protection function
As a protection function of the electronic load device, 8 types of protection circuits are implemented to support safe test operation.

control interface
LAN (Ethernet) and PLC interface are common and standard equipment. Remote control including automation from the host PC is possible.

Emergency stop button
Equipped with an emergency stop button, which is essential in the car electronics industry. During operation, the power line gate is blocked (forcibly opened by the conductor). It is guarded to prevent malfunction, and external control (Di input) is also possible.

Specification
type name | NT-AD-50KD-B | NT-AD-50KH-B | NT-AD-50KO-B | |
---|---|---|---|---|
Basic function
|
||||
Output range | ![]() |
![]() |
![]() |
|
Rating | Rated power | 50kW | ||
Rated voltage | 350V | 750V | 1500V | |
Rated current | ±300A | ±200A | ±100A | |
Minimum operating voltage | 0V | |||
ripple current | Within 4Ap-p (switching frequency component) | |||
Regenerative efficiency | Up to 90% or more (at rated input/output) | |||
Constant voltage (CV) mode | Voltage setting range | 0-350V | 0-750V | 0-1500V |
Setting resolution | 0.1V | |||
Setting accuracy | ±0.3% of F.S. | |||
response time | Within 50msec (10% to 90%) | |||
transient recovery time | Within 20msec | |||
Power running ⇔ regenerative switching function | Automatic switching | |||
Constant current (CC) mode | Current setting range | 0 to ±300A | 0 to ±200A | 0 to ±100A |
Setting resolution | 0.3A | 0.25A | 0.125A | |
Setting accuracy | ±0.3% of F.S. | |||
response time | Within 10msec (10% to 90%) | |||
Power running ⇔ regenerative switching function | Manual switching | |||
Constant power (CP) mode | Power setting range | 0 to ±50kW | ||
Setting resolution | 20W | |||
Setting accuracy | ±0.5% of F.S. | |||
response time | Within 10msec (10% to 90%) | |||
Power running ⇔ regenerative switching function | Manual switching | |||
soft start | 0, 1, 2, 5, 10sec | |||
Measuring part
|
||||
Voltage measurement | Voltage measurement range | 0.0 to 350.0V | 0.0 to 750.0V | 0.0 to 1500.0V |
Measurement resolution | 0.1V | 0.1V | 0.2V | |
Measurement accuracy | ±0.3% of measure. ±1V | ±0.3% of measure. ±1V | ±0.3% of measure. ±2V | |
Current measurement | Current measurement range | 0.0 to ±300.0A | 0.0 to ±200.0A | 0.0 to ±100.0A |
Measurement resolution | 0.15A | 0.125A | 0.0625A | |
Measurement accuracy | ±0.3% of measure ±0.3A | ±0.3% of measure.±0.25A | ±0.3% of measure ±0.125A | |
Power measurement | Power measurement range | 0 to ±50kW | ||
Measurement resolution | 20W | |||
Measurement accuracy | ±0.5% of measure ±62.5W | |||
Limit function
|
||||
Voltage limit | Voltage setting range | 0-360V | 0-760V | 0-1520V |
resolution | 1V | 1V | 2V | |
Operation at limit | Triggers an alarm at the set limit value. Stop output | |||
current limit | Current setting range | 0 to ±300A | 0 to ±200A | 0 to ±100A |
resolution | 0.3A | 0.25A | 0.125A | |
Operation at limit | Clip current at set limit | |||
power limit | Power setting range | 0 to ±50kW | ||
resolution | 20W | |||
Operation at limit | Clip power at set limit | |||
protective function
|
||||
emergency stop | Emergency stop of the device is performed by pressing the emergency stop button on the rack. | |||
Overvoltage protection | 390V | 780V | 1560V | |
Overcurrent protection | 330A | 220A | 110A | |
over power protection | 51.5kW | |||
Overheat protection | 90℃ (switching element temperature) | |||
low voltage protection | -2V | |||
Internal overvoltage protection | 480V | 960V | 1920V | |
Reverse connection alarm | -2V | |||
Grid protection function
|
||||
Overcurrent protection | 82 Arms | |||
Overvoltage protection | 435 to 465Vrms / Resolution 10Vrms / Detection time 0.1 to 2.5sec | |||
undervoltage protection | 325 to 355Vrms / Resolution 10Vrms / Detection time 0.1 to 2.5sec | |||
over frequency protection | 50.0 to 65.9Hz / Resolution 0.1Hz / Detection time 0.0 to 9.9sec | |||
Under frequency protection | 45.0 to 60.9Hz / Resolution 0.1Hz / Detection time 0.0 to 9.9sec | |||
Islanding detection passive | Voltage phase jump detection / Detection level 2 to 10° / Enable/disable selectable | |||
Islanding detection active | Reactive power fluctuation method / enable/disable selectable | |||
Other features
|
||||
remote sensing | function | Compensation for voltage drop of electric wire (up to 10V one way) | ||
EXT IN jack (rear panel) | Rear terminal block (M6) | |||
Parallel operation | Maximum number of parallel units | 5 pieces | ||
Maximum rated voltage/current/power | DC 350V ±1500A 250kW | DC 750V ±1000A 250kW | DC 1500V ±500A 250kW | |
Series operation | Maximum series number | 2 units (parallel is not possible when connected in series, factory option) | Series connection not possible | |
Maximum rated voltage/current/power | DC700V±300A100kW | DC 1500V ±200A100kW | ||
External control signal output/input
|
||||
Digital I/O | load on/off | Photo coupler input (DC12-24V/8mA) | ||
Protection/alarm status | Photocoupler output open collector (DC24V/10mA, recommended 1mA) | |||
Operation mode setting | Photo coupler input (DC12-24V/8mA) | |||
emergency stop | Photo coupler input (DC12-24V/8mA) | |||
analog input | input voltage | 0-10V | ||
Setting items | CC, CC limit, CV, CV limit, CP, CP limit | |||
Analog output voltage monitor |
monitor output | 0-10V / 0-500V | 0-10V / 0-1000V | 0-10V / 0-2000V |
output impedance | 50Ω | |||
terminal | BNC / isolated output | |||
Analog output current monitor |
monitor output | -10~10V / -300~300A | -10 to 10V / -200 to 200A | -10 to 10V / -100 to 100A |
output impedance | 50Ω | |||
terminal | BNC / isolated output | |||
interface
|
||||
LANs | Communication specifications | IEEE 802.3 | ||
connector | RJ45 | |||
data rate | 10Base-T 100Base-TX | |||
RS-232C | connector | D-sub 9pin | ||
General specifications
|
||||
Power supply | Input rating | Grid side: 3-phase 3-wire 400±40V, 50 Hz ±2 Hz or 60 Hz ±2 Hz overvoltage category II |
||
Power factor | at maximum load | 0.9 or more | ||
input power | No load | 800 VA or less | ||
Input current | At maximum load (at AC400V) | 73 Arms | ||
At maximum load (at AC360V) | 89 Arms | |||
Recommended breaker | AC 100A | |||
Terminal block screw diameter | Power output terminal block | M12 | M10 | M6 |
System input terminal block | M6 | |||
Remote sense terminal block | M6 | |||
mass | only a main part | About 950kg or less | ||
External dimensions | Not including protrusions | W600×H1977.5×D900mm | ||
Environmental condition | Operating environment | indoor use | ||
operating temperature | 0°C to +40°C | |||
operating humidity | 20 %rh to 85 %rh (non-condensing) | |||
storage temperature | -20°C to +60°C | |||
storage humidity | 20 %rh to 85 %rh (non-condensing) | |||
Altitude | 2000 m or less | |||
cooling method | Forced air cooling by fan | |||
Withstand voltage | Between input and output | No abnormality after applying 1800 V AC for 1 minute | ||
Between input and FG | No abnormality after applying 1800 V AC for 1 minute | |||
insulation resistance | Between input and FG | 500 VDC, 30 MΩ or more | ||
Compliance standard | EMC standards | EN61000-3-2 | ||
CE | Low Voltage Directive 2014/35/EU | |||
Safety standard | IEC 61010-1 | |||
option
|
||||
AX-OP01 | Master-slave cable 1m | Master-slave cable 1m | ||
AX-OP02 | Master-slave cable 3m | Master-slave cable 3m | ||
AX-OP13 | System side three-phase three-wire 200V option | Grid input voltage 3-phase 200V±20V 50Hz/60Hz change (factory option) |