This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.
ITEMLIST
Products Infomation
Effective diagnostics to maintain the performance and operation of critical facilities
SOKEN Model DAC-PD-9A is a digital partial discharge analyzer that applies to IEC 60270, which is referenced in a variety of IEC standards for PD measurement.
DAC-PD-9A provides narrow band, wide band and ultra-wide band measurement up to 40MHz, which enables to select an appropriate frequency band for each specimen.
All data will be sampled in time series, and statistical measurement can be performed. In the wide band measurement, the positive and negative polarities of the discharge waveform are discriminated and displayed. The further analysis is possible by creating graphs with the stored data.
Digital Partial Discharge Analyzer
Model:
DAC-PD-9A
Maker:
SOKEN ELECTRIC CO.,LTD.
Features
- Digital technology enables analysis of the true partial discharge patterns.
- All parameters such as cumulative frequency of occurrence and net peak are displayed in real time.
- Discharge pulses of positive and negative polarities can be counted simultaneously.
- Free center frequency and frequency bandwidth selection provide the optimum frequency band for each measurement.
- The large-capacity memory enables long-term data storage.
- Simple and visual operation with TFT liquid crystal touch screen.
- Light weight and compact body (W320 × D350 × H150 mm, 8 kg).
- USB interface and LAN for communication.
Examples of use
- Transformer
- Generator
- Motor
- Coil
- Insulation Materials
- Circuit Breaker
- Switch
Specifications
| DAC-PD-9 Measurement Specifications | ||
| Maximum Partial Discharge | Measuring Range | 1 – 100000 pC |
| Phase Resolution | 1 degree | |
| Evaluated Occurrence Frequency | 1 – 400 pps | |
| Occurrence Frequency | Measuring Range | 0 – 99999 pps |
| Polarity | Auto discrimination | |
|
Frequency Band Width Low band: 0 Hz – 400 kHz MID band: 400 kHz – 4 MHz HIGH band: 4 MHz – 40 MHz |
Center Frequency | 50 kHz – 40 MHz |
| Low | 50 kHz, 100 kHz, 300 kHz | |
| MID | 300 kHz, 500 kHz, 1 MHz, 3 MHz | |
| HIGH | 300 kHz, 500 kHz, 1 MHz, 3 MHz | |
| Gain | -40 dB to 116 dB | |
| Input Characteristic | Input Impedance | 50 ohm |
| Input Voltage Range | 0 – 25 V p-p | |
| Memory | Max 3000 cycles (Number of cycles of power supply frequency) | |
| Voltage Detection (Trigger Source) | ||
| Input Characteristics | Input Impedance | 2 M ohm |
| Input Voltage Range | 0 – 20 V rms | |
| Input Frequency Range | 50 – 400 Hz | |
| Other Specifications | ||
| Interface | USB 2.0/1.1, B type connector, LAN | |
| Size and Weight | W320 × D350 × H150 mm, approx. 8 kg | |
| Input Power | AC 100, 115, 220 or 240 V ±10%, 50/60 Hz | |
| Operation Condition | Temperature 0 – 40 °C / Humidity 20 – 85% (no dew) | |
| Software | ||
| Operating OS | Windows 10, 11 | |