HIOKI AC LEAKAGE CLAMP METER CM4003 (Output and external power supply function)

AC LEAKAGE CLAMP METER CM4003 (Output and external power supply function)

Prevent unexpected downtime!
Identify potential problems and avoid large problems

AC LEAKAGE CLAMP METER

Model:

CM4003

Maker:

HIOKI

Feature

  • Easily transfer measurement data to your smartphone or tablet by using our free app GENNECT Cross or to an Excel® file. (Wireless Adapter Z3210 is necessary)
  • Complies with the performance standard set forth in IEC/EN 61557-13, an international standard on leak clamp meters
  • Output function (waveform/RMS): use with a recorder to record waveforms and fluctuations
  • Detect minuscule leakage currents with a newly designed sensor. (Core jaw diameter up to φ 40 mm)
  • Solve GFCI and RCD problems quickly
  • External power supply: use an optional AC adapter for continuous, long-term measurement
  • Broad measurement range extending from leakage currents to load currents
  • Speed up pass/fail judgments with the built-in comparator function
  • CAT III 300 V

Product Video

Specification

AC Current range 6.000 mA, 60.00 mA, 600.0 mA, 6.000 A, 60.00 A, 200.0 A, 6 ranges, True RMS
Basic accuracy 45 Hz – 400 Hz: ±1.0% rdg ±5 dgt (6.000 mA to 6.000 A), ±1.5% rdg ±5 dgt (60.00 A, 200.0 A)
Basic accuracy 15 Hz – 45 Hz, 400 Hz – 2 kHz: ±2.0% rdg ±5 dgt
Defined accuracy range: 0.060 mA to 200.0 A
AC Voltage range N/A
Frequency range 15.0 Hz to 2000 Hz
Crest factor 3 (other than 200.0 A range), 1.5 (200.0 A range)
Filter function Cut off frequency: 180 Hz ±30 Hz at filter ON (-3 dB)
Output function RMS (RMS value output), WAVE (waveform output)
Harmonic levels [With Z3210 installed] Current harmonic levels up to 30th, Content factor, Total harmonic distortion ratio
*Harmonics can be displayed with our free app GENNECT Cross.
Other functions Max/ Min/ AVG/ PEAK MAX/ PEAK MIN value display, Display value hold and auto hold; Backlight, Auto power save, Buzzer sound, Event count display, Comparator, Simple event recording, Rush current measurement
Display Display refresh rate: 5 times/s
Power supply – AA-size alkaline battery (LR6) × 2; Continuous operating time: 48 hr. (without Z3210 installed), 30 hr. (with Z3210 installed and using wireless communications)
– AC Adapter Z1013 (5 V DC, 2.6 A)
Core jaw diameter φ 40 mm (1.57 in.)
Dimensions and mass 64 mm (2.52 in) W × 233 mm (9.17 in) H × 37 mm (1.46 in) D, 400 g (14.1 oz.)
Included accessories Connection Cable L9097 × 1, USB Cable × 1, Carrying case C0203 × 1, Instruction manual × 1, Operating Precautions × 1, AA-size alkaline battery (LR6) × 2